Key Takeaways
- Read the spec for what the wall must do, then work through the twelve questions in order. Each one drives a single decision.
- The first group sets density and panel length. The second sets thickness and reinforcement. The third sets face tolerance and piece size. The fourth locks the final grade.
- Over-specifying adds cost the wall never needed. Under-specifying can lead to rejection at PE submission and a re-tender of the wall package.
- Compressive strength locks density. Higher strength cannot be pulled out of a low-density panel, because the mix changes.
Choosing an ALC wall panel starts with the architect’s specification, but the spec rarely names a panel. It describes what the wall must do, such as the acoustic performance it needs, the fire rating it must meet, how high it must stand and how it will be finished.
To turn those requirements into a panel, we read every spec through the same twelve questions, in the same order. Each question settles one decision, such as density, thickness, length or reinforcement. By the last answer, the panel has specified itself.
These are the questions we use to specify an ALC panel. The article goes through the twelve questions in four groups. For each one, it shows the standard answer and the step-up that applies when the spec asks for more.
Why the Order of the Twelve Questions Matters
The questions build on one another, so answering them out of order means revisiting decisions already made. The order also protects against two costly outcomes.
The first is over-specifying. A 1,200 kg/m³ acoustic panel on a partition with no STC call-out adds cost the wall never needed. The second is under-specifying. A panel that falls short of the spec can be rejected at PE submission, and the wall package then re-tenders weeks into the programme.
What the Wall Must Do: STC, Fire Rating and Buildability
The first three questions cover performance and certification. Their answers set the density and the panel length.
What Is the STC Requirement?
With no STC call-out, density only has to satisfy compressive strength, so a structural grade is enough. When an STC value is specified, acoustics now drive density, and 1,100 to 1,200 kg/m³ should be priced in.
What Is the Fire Rating?
This question drives nothing, because the rating is already certified. vPANEL carries an independent COC with a 4-hour rating, certified across 100 to 200 mm, and the 2-hour and 3-hour ratings sit under the same certificate. There is no upgraded build, no special order and no premium, so on most projects fire rating is a non-decision.
Does Buildability or CONQUAS Matter?
With no scoring target, panel length is open and the crew picks the most economical cut pattern. When the project is chasing a CONQUAS score, the answer steps up to fewer joints and tighter tolerance, with a vertical cast of 4 to 6 m and no horizontal joints.
What the Panel Must Resist: Deflection, Height and Span
The second group covers span and load. Its answers set the panel thickness and the reinforcement.
What Is the Deflection Criterion?
Internal partitions and short external runs use the default cage: one layer of 5 to 6 rods at 4 mm. A long span, a wind load, or a PE who wants the stiffener designed out steps up to two layers of 8 rods at 5 mm.
How High Is the Wall?
At 4 m or below, 100 mm holds comfortably for internal or short external walls. External walls above 5 m under wind step up to 150 to 200 mm, which keeps the wall inside the L/240 to L/300 deflection range.
What Is the Column-to-Column Span?
A span of 4.2 m or less is carried by 100 mm with the default cage, which takes the bending moment. Beyond 4.2 m, the options are to thicken to 150 to 200 mm, upgrade the cage, or stiffen every 4.2 m.
How the Wall Goes Up: Finish, Installation and Site Access
The third group covers how the wall is finished and installed. Its answers set face tolerance and piece size.
Should the Wall Be Skimmed or Plastered?
The standard answer is cement-sand plaster on both faces, where the 10 mm render absorbs face variation. Direct skim with no plaster steps up the requirements, because flatness becomes critical. That calls for a laser-levelled installation and a tighter-tolerance grade.
Should Panels Be Installed Vertically or Horizontally?
External walls and full-height partitions suit vertical installation: panels cast to 6 m, set slab to soffit, with joints at the top and bottom only. For short infill or a restricted lift, horizontal panels at 600 × 1,200 mm work, but they leave a joint every 600 mm.
What Site Limitations Apply?
Clear access allows full-length panels, which means fewer joints, faster installation and a lower accessory bill. Low headroom, a narrow lane or limited crane reach calls for a 1.5 m short panel, sectioned cuts or a horizontal cast.
Locking the Final Grade: Strength, Waterproofing and Lintels
The last group fixes the density and decides which in-situ work disappears.
What Compressive Strength Is Required?
Strength locks density, and it is not negotiable. A requirement of 3.5 MPa or more means 650 kg/m³ wet and 550 kg/m³ dry. A requirement of 7 MPa or more means 950 wet and 850 dry. A requirement of 10 MPa or more means 1,200 wet and 1,100 dry. Higher strength cannot be pulled out of a low-density panel, because the mix changes.
Is Waterproofing or Thermal Performance Specified?
If neither is specified, the panel stays standard and the wall package stays lean, so there is no need to price them in. When a U-value or λ is stated, as in a cold room, a data centre or an insulated façade, the answer is a lower-density panel or an added insulation layer.
Can the Lintel and Stiffener Be Reduced?
On short walls, keep the default mid-height stiffener and the cast-in-situ lintel over openings. When the cage from the deflection question and the thickness from the height and span questions are stepped up, the panel spans with no stiffener and carries the lintel zone. That removes in-situ work and leaves fewer trades on the critical path.
The Panel After Twelve Answers
Once all twelve questions are answered, the panel is fully defined. Thickness is 100, 150 or 200 mm, and length runs from 1.5 m to 6.0 m. Density ranges from 550 to 1,100 kg/m³. Reinforcement is either the default cage or two layers of 8 rods at 5 mm. Orientation is vertical or horizontal, and the finish is plaster or direct skim.
What Vodapruf Offers for Your Wall Specification
We make vPANEL at our factory in Johor, and the panel range covers each outcome described above: thicknesses of 100, 150 and 200 mm, lengths from 1.5 m to 6.0 m, and densities from 550 to 1,100 kg/m³. The fire rating is covered by the independent COC with a 4-hour rating, so it stays a non-decision on most projects.
Our process starts with the specification itself. We run your architect’s spec through the twelve questions before a single line is priced, so every item in the BQ is defended by a clause in the spec. The benefit for you is a panel matched to what the wall must do, without paying for an over-specified grade or risking an under-specified one at PE submission.
Beyond the panel, quotation, shop drawings, DOC submission and delivery are handled by one team. The skim coat and jointing mortar come with the panel, and our technical team supports installers on site with training and technical guidance.
How Can You Have Your Spec Checked Against the Twelve Questions?
Send us the architect’s specification PDF and we will run it through the twelve questions. You can reach us on WhatsApp or email to inquiry@vodapruf.com.
📞 Malaysia: +60 16 217 7155
📞 Singapore: +65 9796 5910
🌐 vodapruf.com
Frequently Asked Questions
What STC values can an ALC wall panel reach?
The STC report in our compilation (TÜV SÜD PSB, ASTM E90, 2017) measured STC 38 for a 100 mm vPANEL. Our acoustic chart gives higher ranges for added finishes and density: 47 to 49 at 650 kg/m³ with 10 mm plaster and 5 mm skim on both sides, and 63 to 66 for a twin-leaf wall at 1,200 kg/m³.
Is an ALC wall panel suitable for wet areas?
Yes, vPANEL is listed as suitable for wet areas and for external walls. Water absorption was tested by capillary action to BS EN 772-11. Waterproofing and thermal requirements are decided separately, and the panel stays standard when neither is specified.
Which test reports and certificates support an ALC wall panel submission?
Our compilation holds 16 test reports and certificates. These include the SIRIM fire test to BS 476 Part 22, a TÜV SÜD PSB fire assessment and certificate of conformity, a non-combustibility test, SGBC product certification and CIDB IBS certification. It also holds a Bomba fire safety installation certificate.
Is an ALC wall panel non-combustible?
vPANEL is classified as non-combustible to BS 476 Part 4 (TÜV SÜD PSB report 7191281711-MEC22, 2022). Separately, SIRIM’s BS 476 Part 22 test on a 100 mm panel with 5 mm skim on both sides recorded 240 minutes for integrity and for insulation. One describes the material, the other how the wall performs in fire.
How does a vPANEL short panel compare with AAC blocks?
On a 3 × 3 m wall, our comparison sets 600 × 1,500 mm short panels against 600 × 200 mm AAC blocks. Grout joints fall from 54 m to 15 m, and installation is 7.5 times faster. The short panel is non-reinforced, so it suits short-span partition walls.
Does vPANEL have green certification for Singapore projects?
vPANEL holds SGBC product certification and the SEC Green Label certificate. Its test reports also include a VOC and formaldehyde emission test (SETSCO, ASTM D5116) and a 7-day emission test. Check each project’s own green requirements against these certificates before submission.
Can an ALC wall panel be used for a data centre wall?
Yes, ALC panels for data centres include our DAYONE Data Centre project in Kempas, Johor Bahru (JB), which uses a 100 mm and 200 mm vPANEL wall system. Where a U-value or λ is stated, the spec can call for a lower-density panel or an added insulation layer.